Veichi SI23 & SI30 First Set-up (Solar Pumping Application)

THE FIVE SETTINGS REQUIRED FOR A BASIC SI23 SETUP Main Menu: F00 sub-menu: F00.12 is low-speed cut-off frequency Hz Main Menu: F05 sub-menu: F05.02 is motor size selection kW Main Menu: F05 sub-menu: F05.04 is operational speed RPM Main Menu: F05 sub-menu: F05.06 is amps for motor A Main Menu: F14 sub-menu: F14.14 is low speed protection detection frequency Hz (Example is 1.1kW - use your AC pump specs and change accordingly). SI30 uses same settings but an external programming keypad needs to be plugged into the unit to program it. www.cedarsolar.com