#198 N4 Tridium Niagara - Edge-10 using DOs to switch AO2 output

Tridium Niagara Edge 10, used for fan coil control only, has 2 analogue outputs. If you have a cooling/heating valve, that is fine, but if you also have an analogue 0-10VDC fan speed, you don't have an additional AO for the fan speed. This video shows you how to use two Digital outputs to switch AO2 for the heating and cooling actuators. Tridium’s Niagara Edge 10 is an IP-based field equipment controller powered by the Niagara Framework®. Niagara EDGE 10 controllers drive applications such as zone temperature control, and the operation of fan coil units, single-stage air handling units, water-source heat pumps and more. Connection: Counts as only 1/10 of a standard supervisor connection Niagara Edge 10 controllers run the full Niagara Framework stack, with 10 points of on-board IO and IO-R-34 expansion capability. Niagara Edge 10 licensing supports three devices and 50 total points, enabling full Niagara at the edge. HARDWARE SPECS: NXP iMX6 SoloX2: 800MHz ARM Cortex-A9/M4 512 MB DDR SDRAM 2GB total eMMC flash storage with user space set at 1GB Powered from 24VAC/DC source 5 Universal input: Type 3 (10K) thermistors, 0-100K ohm, 0-10VDC, 0-20mA with external resistor, Dry Contact 2 Analog outputs: 0-10VDC, 4mA max output current 3 Digital outputs: Triac, 24VAC @.5 amp 2 10/100MB Ethernet ports capable of daisy chaining 1 RS-485 serial port Real-time clock Secure boot NETWORK: Niagara Edge 10 controllers can be daisy-chained to continue network connectivity and eliminate the need for separate wiring back to a switch. Connect Niagara Edge 10 controllers to your main building or IT network and manage them directly with a Supervisor alongside a JACE®. Use the secondary Ethernet port on the JACE 8000 to create a private network for 10 Niagara Edge controllers. SUPPORT MOUNTING: EN50022 standard 7.5mm x 35mm DIN rail or panel mounting Datasheet at https://hvacproducts.co.uk/product/ed...