Seplos V3 BMS Settings Improved

NOTE: See Data Logger Updates below. Recommended settings which are less conservative than previous settings. A must do if using more than one battery pack. Settings may vary depending on your cell capacity. The changed pack and cell parameters are: May 2025 (Stop the OV-ILLC alarm at 100% SOC) Battery High Voltage Recovery = 57.6V Battery High Voltage Alarm = 58.4V Battery Over Voltage Recovery = 57.6V Battery Over Voltage Protection = 59.2V Cell High Voltage Recovery = 3.6V Cell High Voltage Alarm = 3.65V Cell Over Voltage Recovery = 3.6V Cell Over Voltage Protection = 3.7V Charge Voltage 57.5V Data Logger Update: Some people have found that their data logger stops communicating after adding a battery. This can happen when the baudrate on the inverter is changed from the 9600 default on the Solis/Ginlong Inverters. Simply change the baudrate back to default on the inverter. DO NOT CHANGE the higher baudrate on the BMS studio, as this needs to be higher to connect to the BMS. Reboot the system when there is no solar load on it and your Solis inverter should start to communicate with the datalogger again.