INVT VFD CHF100 A Run Through Keypad and Digital Inputs Terminals and INVT Inverter Parameters.

INVT VFD CHF100 A Run Through Keypad and Digital Inputs Terminals and It's Related Parameters. Keppad Control: parameter No. PO.01. Select to 0 for Run Keypad operation. Parameter No. PO.07. Select to 0 for Keypad Frequency operation then we can change the frequency through UP and Down Key. Digital Inputs Terminals: parameter No. PO.01. Select to 1 for Run operation through Digital terminals, Digital Input Terminals will be Active. we will Short S1 and Com VFD Run. Parameters No. PO.07: Select to 1 for Control Frequency operation through Digital Input Terminals then we can change the frequency through Digital Input Terminal No. Gnd ,AI1 and +10 V these Connection for Potentiometer If we haven't Potentiometer then we can short AI1 and +10V for Frequency Control. Parameter No. P5.01- Select the P5.01 to 1 for S1 to Forward Enable parameter No. P5.12- Select to 0V for Minimum Frequency Control reference. parameter No. P5-14- Select to 10V Maximum Frequency Control reference.