How to by-pass Standard 1 compressor | Daikin VRV3 | ermergency setting.
Brand : Daikin VRV 3 model : RXQ14PAY13 Error : E6 Cause : Standard 1 compressor jammed Action : By-pass standard 1 compressor for temporary use. (Ermergency setting) Ermergency setting for standard 1 compressor, 1)press mode button more than 5 seconds (until H1P light up) 2)press set button 19 times. 3)press return button once. 4)press set button once. 5)press return button once. 6)press mode button to exit. #bonmj #daikin #vrv

▶︎